Basic Info.
Model NO.
LZZBJ9-10A
Insulating Medium
Epoxy Resin
Installation
Strut Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Type of Current Transformer
Indoor Use,Epoxy Resin,Sealed Structure
Rated Voltage
11kv
Applicable Standard
IEC60044-1, IEC61869-2
Combined Accuracy Classes
0.2/10p10, 0.5/10p10
Transport Package
1PCS/CTN
Specification
15/5/5A
Trademark
DHECN
Origin
China
HS Code
8504311000
Production Capacity
5000PCS/Month
Product Description
LZZBJ9-10A Type Current Transformer
Applications |
LZZBJ9-10(A) current transformer is suitable for power measurement, current monitoring and relay protection in power system with rater frequency 50Hz or 60Hz and rater voltage 10kV. Applicable Standard: IEC60044-1, GB 1208 . |
Operation Conditions |
Installation area: Indoor. Ambient temperature: Max. temperature 40ºC;Min. temperature -5ºC;Daily average temperature can't exceed 30ºC. Air conditions: No heavy pollution in air. |
Technical Parameter | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Rated secondary current: 5A or 1A. Rated insulation level:12/42/75kV. |
Structure and Feature |
Current transformer have the whole-sealed structure with epoxty resin as its main insulation. Its core adopts the crystallitic alloy or excellent silicon steel sheets to enwind becoming annular, then secondary leads are enwinded on it evenly. Primary conducts are winded by insulation belt to avoid short circuit between conducts. There are earth bolts and holes suitable for mounting on the bottom of the product suitable the mounting. |
Information Required for Order Placing |
Model. Rated current ratio A. Combined accuracy classes and Rated output VA. Altitude m. |