Basic Info.
Model NO.
YB-0.4-12
Form
All- packaged Type
Operation Voltage
High Pressure/Low Pressure
Size
According to Custom Standards
Application Range
High-rise Buildings
Shell Material
Stainless Steel
Shell Protection Grade
IP33
Brand
Bo Lian
Rated Voltage
0.4/10kv
Rated Frequency
50Hz
Transport Package
Iron Case/Wooden Case
Specification
According to custom standards
Trademark
BO LIAN
Origin
China
Packaging & Delivery
Package Size
1500.00cm * 1500.00cm * 2000.00cm
Package Gross Weight
1000.000kg
Product Description
YB-12/0.4- high-voltage / low-voltage pre-assembled substation (referred to as box variable or European box variable), is the high-voltage electrical equipment, transformers, low-voltage electrical equipment, etc., combined into a compact set of power distribution equipment, high-rise buildings in urban and rural areas, urban and rural buildings, residential districts, high-tech development zones, small and medium-sized factories, mines and oilfields, as well as temporary construction of electricity and so on, for the distribution system for the acceptance and distribution of electrical energy.
The metal-type box substation is riveted by composite plate and aluminium alloy or galvanized steel plate, etc., and its internal partitions made of angle steel and galvanized steel plate are divided into functional compartments; the top of the box substation is made of high-quality steel plate double-welded and sprayed by surface treatment, and the top of the box substation is fitted with special glass tile roof, and there is a special water drainage channel to prevent the accumulation of water.
The metal-type box substation is riveted by composite plate and aluminium alloy or galvanized steel plate, etc., and its internal partitions made of angle steel and galvanized steel plate are divided into functional compartments; the top of the box substation is made of high-quality steel plate double-welded and sprayed by surface treatment, and the top of the box substation is fitted with special glass tile roof, and there is a special water drainage channel to prevent the accumulation of water.
NO | UnitTechnical Parameters | Unit | Technical Parameters |
1 | Rated Voltage | KV | 10/0.4(HV/LV) |
2 | Maximum Working Voltage | KV | 12(High voltage side) |
3 | Rated Frequency | HZ | 50 |
4 | Rated Capacity | KVA | 50-1600 |
5 | 1Min Working Frequency Withstand Voltage | KV | 35 |
6 | Lightning Impulse Voltage | KV | 75 |
7 | Cooling Mode | ONAN | |
8 | High Voltage Backup Fuse Breaking Current | KA | 50 |
9 | Breaking Current Of Plug-in Fuse | KA | 2.5 |
10 | Ambient Temperature | ºC | -35~+40 |
11 | Coil Allows Temperature Rise | ºC | 65 |
12 | No Load Voltage Regulation | ±5% or ±2×2.5% | |
13 | Noise Level | db | 50 |
14 | Class Of Protection | IP43 |